- Dual flooding areas
- 6 detection zones
- Approved to EN12094-1, EN54- 2, EN54-4
- Fully configurable zone voting for gas release
- 6 programmable sounder circuits
- Configurable sounder delays
- Zero time delay option for manual call points
- Compatible with IS barriers
- Non-latching zone input option
- Extinguishant delay 0-60 seconds
- Extinguishant duration 1-300 seconds
- Flooding time 60-1800 seconds
- Extract time 1-900 seconds
- Graphical back lit LCD display
- Access controls via key switch or code entry
- Time and date stamped event log
- Alarm counter
- Company logo can be programmed in display
- RS 485 communications for remote status units
- Optional key switch status control
- Fire, fault & stage signal relays
- 2 amp actuator circuit
- Hold, abort, flow switch, manual release, mode control and pressure switch monitoring inputs
- 3.4 amp PSU for 18Ah batteries
TECHNICAL SPECIFICATION
| Enclosure | 1.2mm Mild Steel IP30. Colour ref MW334E Interpon Powder coat |
| Cable Entry | Via 20mm knockouts located in the top and rear of the cabinet |
| Dimensions | Back box: 450 W x 385 H x 100 D (mm), Lid: 463 W x 394 H x 25 D (mm) |
| Mains Supply | Universal switch mode PSU, 3.4A |
| Battery Capacity | Up to 18Ah 24V |
| Charger Current | 700mA |
| Auxiliary Supply | 400mA aux supply output (21-28vdc) |
| Detection Zones | 6 x conventional zones |
| Extinguishing Zones | 2 x flooding/extinguishing zones support for metron & solenoid type actuators |
| Sounder Circuits | 6 x 400mA 21-28vdc |
| On Board Relays | 10 x 1A 30VDC relay outputs, (fire, fault, stage 1 & 2, extract, local) x2 |
| Programmable Outputs | Additional outputs via add on output card, ESG-2005. (1 card per flood zone) |
| Switch Inputs | CC, PULS |
| Monitored Inputs | Flow, Pressure, Release, Hold, Abort x 2 |
| Countdown Timers | Extinguishant Delay: 0-60 secs, Extinguishant Duration: 1-300 secs,
Flooding Time: 60-1800 secs, Extract Time: 1-90 mins, Reset Inhibit Time: 0-30 mins |
| Event Log | 255 events, time & date stamped |
| Earth Fault Monitoring | Yes |
| Intrinsically Safe Mode | Selectable for detection zones |
| Remote Status Units | Graphic display & Mini version via RS485 up to 16 assignable to area |
| Display | 240 x 64 Graphical LCD backlit |
| Manual Release Button | Onboard under plastic release cover x 2 |