4 zone Esento Excel fire alarm control panel, extendable to 12 zones. Excel panels provide the ultimate in flexibility, simplicity & reliability with a generous selection of programmable features, inputs and outputs. Fully networkable up to 8 control panels, 3 false alarm management modes, Twin Wire mode per zone and fully functional repeater panels.
PRODUCT FEATURES:
- 4 zones
- Zonal Twin Wire selection by DIL switch
- Network up to 8 control panels
- Activate controls via key switch or code entry
- Integral detector removal monitoring
- 3 Amp switch mode power supply Nom 27V DC
- 2 monitored sounder outputs
- 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
- Class change I/P
- Alert I/P
- Fire & fault switched -ve outputs
- Program delays to outputs
- False alarm modes A, B & C
- Test mode, with or without sounders
- Disable zones, sounder O/Ps, aux O/Ps & delays
- Alarm load, 2.4A shared between all sounder outputs
- All sounder circuits are fused @ 500mA with resettable fuses
TECHNICAL SPECIFICATIONS:
| Enclosure | 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat |
| Cable Entry | Via 20mm knockouts located in the top and rear of the cabinet |
| Dimensions | Back box: 450mm W x 300mm H x 85mm D, Lid: 460mm W x 310mm H x 25mm D |
| Mains Supply | 3A internal switch mode power supply, Nom 27v DC |
| Battery Capacity | 2 x 7.0Ah 12v VRSLA |
| Detection Zones | 4 x conventional or Twin Wire. EOL = 4K7R |
| Sounder Circuits | 2 x monitored, fused @500mA. EOL = 4K7R |
| Twin Wire | Selectable per zone |
| Networking | Up to 8 control panels, fault tolerant RS485 communication, requires TPCA05 network card |
| On Board Relays | 2 x programmable, 3A, 30v volt free changeover, additional relay provided on high spec zone card |
| Outputs | 2 x programmable, 40mA switch -ve, 2 additional outputs provided on high spec zone card |
| Switch Inputs | Class change & alert (pulsing) |
| Event Log | 40 event history |
| Intrinsically Safe Mode | Selectable per zone |
| False Alarm Management | Type A, B & C dependency modes, approved by LPCB |
| Delay Timer | On board programmable delay timer 1-10 mins |