24 zone Esento Evoque fire alarm control panel. Evoque panels are our large zone format range and provide a generous selection of programmable features, inputs and outputs. Fully networkable up to 8 control panels, 3 false alarm management modes and fully functional repeater panels. (N.B. No Twin Wire mode)
PRODUCT FEATURES
- 24 zones
- Network up to 8 control panels
- Activate controls via key switch or code entry
- Integral detector removal monitoring
- 5 Amp switch mode power supply Nom 27V DC
- 4 monitored sounder outputs
- 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
- Class Change, Alert, Silence Alarms & Reset switched -ve inputs
- Fire, Fault, Disablement & Reset, programmable switched -ve outputs
- Program delays to outputs
- False alarm modes A, B & C
- Test mode, with or without sounders
- Disable zones, sounder O/Ps, aux O/Ps & delays
- Fire alarm routing output programmable option
- Alarm load, 4.25A shared between all sounder outputs
- All sounder circuits are fused @ 500mA with resettable fuses
TECHNICAL SPECIFICATIONS:
Enclosure – 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat
Cable Entry – Via 20mm knockouts located in the top and rear of the cabinet
Dimensions – Back box: 450mm W x 400mm H x 130mm D, Lid: 465mm W x 410mm H x 25mm D
Mains Supply – 5A internal switch mode power supply, Nom 27v DC
Battery Capacity – 2x 18Ah 12v VRSLA
Detection Zones – 24 x conventional. EOL = 4K7
Sounder Circuits – 4 x monitored, fused @500mA. EOL = 4K7
Networking – Up to 8 control panels, fault tolerant RS485 communication, requires TPCA05 network card
On Board Relays – 2 x programmable, 3A, 30v volt free changeover
Programmable Outputs – 4 x programmable 40mA switch -ve outputs
Switch Inputs – Class change, alert (pulsing), silence alarms & reset
Event Log – 40 event history
Intrinsically Safe Mode – Selectable per zone
False Alarm Management – Type A, B & C dependency modes, approved by LPCB
Delay Timer – On board programmable delay timer 1-10 mins