Esprit-G Single Flood Area 3.4A

  • Home
  • Products
  • Esprit-G Single Flood Area 3.4A

Esprit-G Single Flood Area 3.4A

Single flood area Automatic Extinguishant Release control panel with integral 3.4A power supply. Esprit-G control panels are fully configurable for extinguishant release scenarios including flexible zone voting for the gas release and programmable countdown timers to suit the exact requirements of the site. A large graphical display accommodates an easy-to-navigate menu system.

PRODUCT FEATURES

  • Single flooding area
  • 3 detection zones
  • Approved to EN12094-1, EN54- 2, EN54-4
  • Fully configurable zone voting for gas release
  • 4 programmable sounder circuits
  • Configurable sounder delays
  • Zero time delay option for manual call points
  • Compatible with IS barriers
  • Non-latching zone input option
  • Extinguishant delay 0-60 seconds
  • Extinguishant duration 1-300 seconds
  • Flooding time 60-1800 seconds
  • Extract time 1-90 minutes
  • Graphical back lit LCD display
  • Access controls via key switch or code entry
  • Time and date stamped event log
  • Alarm counter
  • Company logo can be programmed in display
  • RS 485 communications for remote status units
  • Key switch status control
  • Fire, fault & stage signal relays
  • 2 amp actuator circuit
  • Hold, abort, flow switch, manual release, mode control and pressure switch monitoring inputs
  • 1.2 amp PSU for 7Ah batteries

TECHNICAL SPECIFICATIONS:

Enclosure 1.2mm Mild Steel IP30. Colour ref MW334E Interpon Powder coat
Cable Entry Via 20mm knockouts located in the top and rear of the cabinet
Dimensions Back box: 350 W x 300 H x 80 D (mm), Lid: 357 W x 310 H x 25 D (mm)
Mains Supply Universal switch mode PSU, 3.4A
Battery Capacity Up to 7 Ah 24V
Charger Current 700mA
Auxiliary Supply 400mA aux supply output (21-28vdc)
Detection Zones 3 x conventional zones
Extinguishing Zones 1 x flooding/extinguishing zones support for metron & solenoid type actuators
Sounder Circuits 4 x 400mA 21-28vdc
On Board Relays 6 x 1A 30VDC relay outputs, (fire, fault, stage 1 & 2, extract, local) x1
Programmable Outputs Additional outputs via add on output card, ESG-2005
Switch Inputs CC, PULS
Monitored Inputs Flow, Pressure, Release, Hold, Abort x 1
Countdown Timers Extinguishant Delay: 0-60 secs, Extinguishant Duration: 1-300 secs, Flooding Time: 

60-1800 secs, Extract Time: 1-90 mins, Reset Inhibit Time: 0-30 mins

Event Log 255 events, time & date stamped
Earth Fault Monitoring Yes
Intrinsically Safe Mode Selectable for detection zones
Remote Status Units Graphic display & Mini version via RS485 up to 16 assignable to area
Display 240 x 64 Graphical LCD backlit
Manual Release Button Onboard under plastic release cover
Scroll to top

SEARCH