4 zone Esento Eclipse fire alarm control panel. Eclipse panels provide a range of our most popular programming features including; false alarm management, Twin Wire mode and non-latching zones. (N.B. No networking or repeater panels).
PRODUCT FEATURES:
- 4 zones
- Twin Wire selection by DIL switch
- Activate controls via key switch or code entry
- Integral detector removal monitoring
- 1.25 Amp switch mode power supply Nom 27V DC
- 2 monitored sounder outputs
- 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
- Class change I/P
- Alert I/P
- Fire & fault switched -ve outputs
- False alarm mode
- Test mode, with or without sounders
- Disable zones, sounder O/Ps & aux O/Ps
- Alarm load, 800mA shared between all sounder outputs
- All sounder circuits are fused @ 500mA with resettable fuses.
TECHNICAL SPECIFICATIONS:
| Enclosure | 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat |
| Cable Entry | Via 20mm knockouts located in the top and rear of the cabinet |
| Dimensions | Back box: 300mm W x 250mm H x 80mm D, Lid: 308mm W x 260mm H x 23mm D |
| Mains Supply | 1.25A internal switch mode power supply, Nom 27v DC |
| Battery Capacity | 2 x 3.2Ah 12v VRSLA |
| Detection Zones | 4 x conventional or Twin Wire. EOL = 4K7R |
| Sounder Circuits | 2 x monitored, fused @500mA. EOL = 4K7R |
| Twin Wire | Selectable in panel |
| On Board Relays | 1 x Fire, 1 x Fault, 3A, 30v volt free changeover |
| Outputs | 1 x Fire, 1 x Fault 40mA switch -ve outputs |
| Switch Inputs | Class change & alert (pulsing) |
| Intrinsically Safe Mode | Selectable per zone |
| False Alarm Management | Type A dependency mode, approved by LPCB |